Is the pressure wrong, or its measurement?

Trace a 4–20 mA loop, collect useful evidence and verify two operating points.

Installation, principle and limits

Ideal two-wire transmitter: I = 4 + 16 × pressure / span in mA, limited here to 0–22 mA. Receiver: 250 Ω; exercise transmitter minimum: 12 V. With insufficient headroom, current is capped at (Vs − 12 V) / (Rline + 250 Ω). This is a teaching simplification, not a product characteristic. Open-loop floating terminals show no fabricated voltage: “—”. Indication is unavailable outside 3.6–21 mA. Noise, HART, precision, internal faults and PT100 are excluded.