Why more amps without more kW?

Measure pump P‑01 in steady operation. Connect voltage, current, power and compensation.

Principle, assumptions and limits

RMS values, three phases separated by 120°, balanced sinusoidal steady state. Rated delta operation at 400 V: Uwinding = Uline, Iwinding = Imotor/√3. In star, Uwinding = Uline/√3. P = 22 × load / 0.90; Qm = P tan(acos(0.82)); Qc = C1 × (U/400)²; Q = Qm − Qc; S² = P² + Q²; I = 1,000 S/(√3 U). Motor efficiency and power factor are held constant, including at reduced load. C1 is at the switchboard, not on an isolated motor. No unbalance, harmonics, capacitor switching transient or self-excitation model.